ASENWARE/LPCB Conventional Fire Alarm System AW-CTD382

AW-CTD382 is conventional photo-electronic heat detector uses a state of-the-art optical sensing chamber. This detector is designed to provide open area protection and to be used with most conventional fire alarm panel.

Inquiry Form

We will get in touch with you shortly

Description

Description

Product Features:
Operating Voltage Range:  9 to 28 VDC Volts Non-polarized
Standby Current:
 ≤120uA@24VDC
Maximum Alarm Current(LED on):
≤15mA@24VDC
(1K Ohm current-limiting resistance)
Operating Humidity Range: ≤95%RH(40℃±2℃)RelativeHumidity,Non-condensing
Operating Temperature Range:  -10℃ to 50℃(14ºF to 122ºF)
Fix Temperature Alarm: 57℃(135ºF)A2R
Rate of rise Alarm: 7.1℃/5S A2R
Height: 48.2mm installed in Base
Diameter: 99.45mm
Standard Number ref: EN 54-7:2000
EC certificate: 0832-CPR-F2072
Technical parameters:
Terminal 6: IN+(Zone Input+)

Terminal 5: IN-(Zone Input-)
Terminal 2: Out+(Zone Output+)
Terminal 5: Out-(Zone Output-)
Terminal 6: Remote Indicator+
Terminal 3: Remote Indicator-