ASENWARE/LPCB Addressable Fire Alarm 32 Zone Control Panel AW-FP300

Asenware LPCB Addressable fire alarm system 32 zone control panel AW-FP300
The purpose of the AW-FP300 Fire Alarm Control Panel (FACP) is to monitor input signals, give indications and possibly activate outputs as programmed.

Inquiry Form

We will get in touch with you shortly

Description

Description

The  Addressable AW-FP300 single loop 32 zone fire alarm control panel offers the following features: 
1. Up to 324 addresses on one loop
2. An easy to read, 4.3” color screen LCD with a resolution of 480×272
3. Zone indication and control panel(ZCP) for 32 zones gives a quick indication of the location of an alarm
4. Record capacity of 1000 historical events for each of historical fire, historical fault and historical operation
5. An independently programmable conventional sounder circuit output
6. Integral power supply and battery
7. Integral printer
8. Flexible and intuitive cause and effect programming on front panel
9. Zone test, point test and module start/stop testing facilitate the commissioning
10. U-disk interface makes the load and save of configuration or historical data convenient for system commissioning and maintenance
11. Hierarchy management with three access levels
12. Anti-tamper protection by a key lock
13. CAN bus for interconnection of up to 20 FACPs and RS485 for connection with up to 30 fire indicating panels per FACP

 

Addressable fire alarm control panel Technical parameters:

 Power supply 
Mains supply 230VAC (-15%, +10%). 47 ~ 63Hz. Max current 0.8A
Mains fuse T3.15AL250V
Operating voltage 18.5 ~ 30VDC
Recommended mains cable Screened or standard/black mains cable, cable size 0.75mm2
Power rating Imax.a=1.2A; Imax.b=2.6A; Imin=0.65A
Max. charging current 1.2A
Max. battery supply current 4A (when the Mains is disconnected)
Battery capacity, type and recommended model Max. capacity 2×12V/17Ah; Min. capacity 2×12V/12Ah
VRLA. PS-12170 for 17Ah (Power-sonic), PS12120 for 12Ah (Power-sonic)
Max. internal resistance of battery 1.5Ω
Battery fuse F8AL250V
Recommended battery cable 14AWG
Quiescent current (full loaded) < 0.4A
Outputs 
S.C. Out (+, -) Output voltage 18.5 ~ 30VDC
Max. output current 0.5A
Fuse rating F1AL250V
End of line resistor 4K7
Recommended type of cable Plain unscreened cable, 1.5mm2
Cable diameter 1mm2 ~2mm2
Transmission distance ≤1500m
Max. number of sounders @50mA 20
F.P.E. Out (+, -)
F.A. Out (+, -)
Output voltage 18.5 ~ 30VDC
Max. output current 0.5A
Fuse rating F1AL250V
End of line resistor 4K7
Recommended type of cable Plain unscreened cable, 1.5mm2
Cable diameter 1mm2 ~2mm2
Transmission distance ≤1500m
Fault Out
(NC, COM, NO)
Contact capacity 30VDC@2A, 125VAC@0.5A
Recommended type of cable Plain unscreened cable, 1.5mm2
Cable diameter 1mm2 ~ 2mm2
24VK (+, -) Output voltage 18.5 ~ 30VDC
Max. output current 0.6A
Fuse rating F1AL250V
Recommended type of cable Plain unscreened cable, 1.5mm2
Cable diameter 1mm2 ~2mm2
Input 
Class change (+, -) Input mode Passive
Cable resistance ≤500Ω
Recommended type of cable Plain unscreened cable, 1.5mm2
Cable diameter 1mm2 ~2mm2
Loop 
Loop Out (+, -)
Loop In (+, -)
Output voltage 16.5 ~ 30VDC, pulse
Output current 0 ~0.3A
Loop type Class A
Recommended type of cable Screened or unscreened twisted-pair, 1.5mm2
Transmission distance ≤1000m
Cable diameter 1mm2 ~2mm2
Network communication 
RS-485 Max. number of FIPs 30
Transmission rate 9600 bps
Recommended type of cable Screened or unscreened twisted-pair, 1mm2
Transmission distance ≤1000m
Cable diameter 1mm2 ~5mm2
CAN Max. number of panels 20
Transmission rate Optional: 10K, 20K, 50K and 100K bps
Recommended type of cable Screened or unscreened twisted-pair, 1mm2
Transmission distance ≤1000m
Cable diameter 1mm2 ~5mm2
Physical dimensions 
Approx. Dimensions of the panel (W×H×D) 430×560×170mm
Approx. weight (without battery) 14kg
Operating conditions 
Temperature range: -5°C~50°C; Max relative humidity: 95%