SIMPLEX Addressable Heat Detector with Base 4098-9733 + 4098-9789

Simplex (4098-9733) Analog Heat Sensor – 067716

The Simplex 4098-9733 TrueAlarm heat sensors are self-restoring and provide rate compensated, fixed temperature sensing, selectable with or without rate-of-rise temperature sensing.  Due to its small thermal mass, the sensor accurately and quickly measures the local temperature for analysis at the fire alarm control panel.

Rate-of-rise temperature detection is selectable at the control panel for either 15° F (8.3° C) or 20° F (11.1° C) per minute.  Fixed temperature sensing is independent of rate-of-rise sensing and programmable to operate at 135° F (57.2° C) or 155° F (68° C).

Inquiry Form

We will get in touch with you shortly

Description

Description

General Features

  • Automatic identification provides default sensitivity when substituting sensor types
  • Integral red LED for power-on, pulsing, or alarm or trouble, steady on
  • Locking anti-tamper design mounts on standard outlet box
  • Magnetically-operated functional test
  • Each device is individually monitored for failure or removal
  • Addressability allows alarms and troubles to be pinpointed to the exact sensor and location
  • All devices are UL268 7th edition listed to meet the latest standards and keep you code compliant