YOKOGAWA Digital YEWFLO Classic Vortex Flow Meter

The digital YEWFLO vortex flowmeter combines the field proven sensor and body assembly used in more than 450,000 units installed worldwide with a unique and powerful combination of digital technology that includes spectral signal processing (SSP), a Yokogawa innovation. The digitalYEWFLO vortex flowmeter is accurate and stable, even in harsh process conditions, and has a highly reliable and robust design that delivers improvements in plant efficiency and reduced operating costs.

Inquiry Form

We will get in touch with you shortly

Description

Description

Standard Type

Model ・DY type vortex flowmeter (Integral type, remote type detector)
・DYA type remote type converter
Specification Standard specification
Measurement Fluid Liquid, gas, saturated steam, superheated steam (avoid multi-phase flow and adhesive fluid)
Process Temperature -29 to 250 °C
Process Pressure -0.1 MPa according to flange rating
Diameter Wafer 15 to 100 mm
Flange 15 to 400 mm
Accuracy Liquid ± 0.75 % of reading (depends on Reynolds number)
Gas, Steam ± 1.0 % of reading (depends on the flow velocity)
Output Signal Analog output, transistor contact output (simultaneous output possible)
Communication Type HART 7 / HART 5, BRAIN, FOUNDATION fieldbus
Explosion Protected Type TIIS Ex d, FM Ex d / Ex ia, ATEX Ex db / Ex ia, CSA Ex d / Ex ia, IECEx Ex db / Ex ia

 

Reduced Bore Type

Model ・DY type vortex flowmeter (Integral type, remote type detector)
・DYA type remote type converter
Specification Optional specifications
1 Size down: /R1
2 Size down: /R2
Measurement Fluid Liquid, gas, saturated steam, superheated steam (avoid multi-phase flow and adhesive fluid)
Process Temperature -29 to 250 °C
Process Pressure -0.1 MPa to flange rating
Diameter Wafer None
Flange R1: 25 to 200 mm (detection unit: 15 to 150 mm)
R2: 40 to 200 mm (detection unit: 15 to 100 mm)
Accuracy Liquid ± 1.0 % of reading (depends on Reynolds number)
Gas, Steam ± 1.0 % of reading (depends on the flow velocity)
Output Signal Analog output, transistor contact output (simultaneous output possible)
Communication Type HART 7 / HART 5, BRAIN, FOUNDATION fieldbus
Explosion Protected Type TIIS Ex d, FM Ex d / Ex ia, ATEX Ex db / Ex ia, CSA Ex d / Ex ia, IECEx Ex db / Ex ia

 

Multi-Variable Type

Model DY type vortex flowmeter (Integral type, remote type detector)
DYA type remote type converter
Specification Optional specifications: /MV
Measurement Fluid Liquid, gas, saturated steam, superheated steam (avoid multi-phase flow and adhesive fluid)
Process Temperature -29 to 250 °C
Process Pressure -0.1 MPa to flange rating
Diameter Wafer 25 ~ 100 mm
Flange 25 to 200 mm (custom specification: 250 to 400 mm)
Accuracy Liquid ± 0.75 % of reading (depends on Reynolds number)
Gas, Steam ± 1.0 % of reading (depends on the flow velocity)
Output Signal Analog output, transistor contact output (simultaneous output possible)
Communication Type HART 7 / HART 5, BRAIN, FOUNDATION fieldbus
Explosion Protected Type TIIS Ex d, FM Ex d / Ex ia, ATEX Ex db / Ex ia, CSA Ex d / Ex ia, IECEx Ex db / Ex ia

 

Combination with Multi-Variable Type Possible

Model Code DY025 to DY100: Wafer Type
DY025 to DY200: Flange Type
Option Code /MV /HT/MV
Function Temperature Indication / Output Temperature Range -29 to 250 °C -29 to 400 °C
Saturated Steam Mass Flow Rate Calculation Temperature Range 100 to 250 °C 100 to 330 °C
Superheated Steam Mass Flow Rate 100 to 250 °C 100 to 400 °C
Gas Volume Flow Rate -29 to 250 °C -29 to 400 °C
Liquid Mass Flow Rate -29 to 250 °C -29 to 400 °C

1. EMC Standards (EMC Standards)

Standard name Standard Type Reduced Bore Type Multi-Variable Type High Process Temperature Version and Cryogenic Version
CE Marking European EMC Directive Yes Yes Yes Yes
RCM Mark Australia and New Zealand
Electrical Equipment Safety Standards
Yes Yes Yes Yes
KC Mark Korea electromagnetic wave conformity standard Yes Yes Yes Yes

2. Explosion Proof Standard

Standard name Standard Type Reduced Bore Type Multi-Variable Type High Process Temperature Version and Cryogenic Version
TIIS Flame proof Yes Yes Yes Yes
IECEx Flame proof Yes Yes Yes Yes (for High Process Temperature Version only)
Intrinsically safe Yes Yes Yes Yes
ATEX Flame proof Yes Yes Yes Yes (for High Process Temperature Version only)
Intrinsically safe Yes Yes Yes Yes
FM Flame proof Yes Yes Yes Yes
Intrinsically safe Yes Yes Yes Yes
CSA Flame proof Yes Yes Yes Yes
Intrinsically safe Yes Yes Yes Yes

3. Communication Protocol

Communication protocol Standard Type Reduced Bore Type Multi-Variable Type High Process Temperature Version and Cryogenic Version
HART 7 Yes Yes Yes Yes
5 Yes Yes Yes Yes
BRAIN Yes Yes Yes Yes
FOUNDATION Fieldbus Yes Yes Yes Yes